120W Industrial DIN Rail Power Supply
Specification
MODEL |
NDR-120-12 |
NDR-120-24 |
NDR-120-48 |
|
OUTPUT |
DC VOLTAGE |
12V |
24V |
48V |
RATED CURRENT |
10A |
5A |
2.5A |
|
CURRENT RANGE |
0 ~ 10A |
0 ~ 5A |
0 ~ 2.5A |
|
RATED POWER |
120W |
120W |
120W |
|
RIPPLE & NOISE (max.) |
100mVp-p |
120mVp-p |
150mVp-p |
|
VOLTAGE ADJ. RANGE |
12 ~ 14V |
24 ~ 28V |
48 ~ 55V |
|
VOLTAGE TOLERANCE |
±2.0% |
±1.0% |
±1.0% |
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
|
LOAD REGULATION |
±1.0% |
±1.0% |
±1.0% |
|
SETUP, RISE TIME |
1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load |
|||
HOLD UP TIME (Typ.) |
16ms/230VAC 10ms/115VAC at full load |
|||
INPUT |
VOLTAGE RANGE |
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] |
||
FREQUENCY RANGE |
47 ~ 63Hz |
|||
EFFICIENCY (Typ.) |
85.5% |
88% |
89% |
|
AC CURRENT (Typ.) |
2.25A/115VAC 1.3A/230VAC |
|||
INRUSH CURRENT (Typ.) |
20A/115VAC35A/230VAC |
|||
LEAKAGE CURRENT |
<1mA / 240VAC |
|||
PROTECTION |
OVERLOAD |
105 ~ 130% rated output power |
||
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
||||
OVER VOLTAGE |
14 ~ 17V |
29 ~ 33V |
56 ~ 65V |
|
Protection type : Shut down o/p voltage, re-power on to recover |
||||
OVER TEMPERATURE |
Shut down o/p voltage, re-power on to recover |
|||
ENVIRONMENT |
WORKING TEMP. |
-20 ~ +70℃ (Refer to "Derating Curve") |
||
WORKING HUMIDITY |
20 ~ 95% RH non-condensing |
|||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
|||
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃) |
|||
VIBRATION |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
|||
SAFETY & EMC |
SAFETY STANDARDS |
UL508, TUV EN62368-1, EAC TP TC 004 approved;(meet EN60204-1) |
||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
|||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH |
|||
EMC EMISSION |
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 |
|||
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020 |
|||
OTHERS |
MTBF |
456.3K hrs min. MIL-HDBK-217F (25℃) |
||
DIMENSION |
40*125.2*113.5mm (W*H*D) |
|||
PACKING |
0.6Kg; 20pcs/13Kg/1.16CUFT |
Patek Philippe and Rolex consistently appear to apperception if top dollar watches appear up in conversation. Examples that were beat alone on break and in excellent or abutting to excellent condition, of course, accompany the a lot of money. Watches with provenance--examples endemic by celebrities or rolex replica fabricated especially for acclaimed individuals--always accept added amount if replica watches uk they appear with adapted documentation.With that said, in her book Vintage Wristwatches (Krause Publications), above Antiques Roadshow adjudicator Reyne Haynes (who now goes by the name Reyne Hirsch) credibility out, "Much like affairs a rolex replica watches monogrammed section of argent collectors generally don't wish anyone else's name, business affiliation, marriage anniversary, etc.